Product Overview:
GKG -/10 (6) series general high voltage switchgear is suitable for use in central control rooms, underground parking lots, and power distribution rooms outside the main ventilation ducts in coal mines with no gas, no dust, and no explosive hazardous areas, as well as other similar metal mines. It is used for distribution protection and control of three-phase AC 50Hz voltage 6kV or 10kV electrical equipment.
This product is also suitable for use in power systems such as coal mines, metal mine ground substations, metallurgy, and chemical industries
Model and meaning:

Main technical parameters:
Rated voltage: 10 (6) kV;
Rated current: 1250 (800, 630, 300, 75) A.
Protection level: IP54
Short circuit breaking and closing current times: "break -0.3s-break -180s-break" 5 times, break 14 times, break 11 times: rated short circuit breaking current: 31.5kA (effective value);
Rated short-circuit closing current: 80kA (peak);
Rated short-time withstand current: 31.5kA (effective value);
Rated peak withstand current: 80kA (peak);
Rated short-circuit duration: 4s;
Rated short-circuit breaking times: 30 times
Main protection functions: 1) Short circuit protection; 2) Overload protection and expansion; It also has functions such as fault memory, fault query, and self check.
Execution standard:
GB/T12173-2008¡¢ Enterprise Standard Q/TG001-2021 "GKG-0/10 (6) General High Voltage Switchgear"
Structure Overview:
The outer shell of the switchgear is made of 2.5mm thick cold-rolled steel plate, which can withstand the impact strength and strength test specified by national standards and the technical conditions of this product. The cable is led into the cable trench and sealed with explosion-proof adhesive after installation. The switchgear is fixed. The unused inlet during installation is blocked with explosion-proof adhesive.
Usage conditions and environment:
Altitude: 1000m;
Environmental temperature: -20¡æ¡«+40¡æ;
Relative humidity: 95%;
In a gas or steam environment that does not damage insulation;
Before installation, check whether the nameplate, specifications, and explosion-proof type meet the requirements.
It is strictly prohibited to open the cover with electricity during use and maintenance.
The cable is led into the cable trench and sealed with explosion-proof adhesive after installation. The switchgear is fixed
The switchgear is equipped with internal and external grounding terminals, which must be reliably grounded during installation
When connecting wires, multiple strands of wire must be crimped with suitable terminal heads and safely pressed onto the terminal blocks. There should be no scattered wire heads outside to avoid discharge.